Messdaten induktiver Sensoren erfassen

Description

The EBIS-TF8-IO16 system of the EBIS IoT product family enables the connection and evaluation of inductive sensors. In addition to the standard features of the EBIS product series, the EBIS-TF8-IO16 unit has 8 half-bridge or 8 LVDT interfaces. Furthermore to the sensor data acquisition, the system provides a trigger input (e.g. for footswitch) or 4 additional independent ADC-Channels (X3 Option). Further, the digital PLC interface with 8 dig. inputs and 8 dig. outputs enables the communication with a PLC and control of extensive automated processes. Due to the available versions and configuration options, a wide range of different sensors can be used and thus a wide variety of applications can be realized.

Acquisition of measurement data from inductive sensors, such as TESA inductive probes, and PLC interface for controlling complete systems.

Technical Characteristics

General Specifications

Power supply
Nominal voltage24V DC
Voltage supply18V – 30V DC
Connector (X1)3-pin. M16 male connector
Ethernet
IP-Adresse192.168.0.17x (configurable)
Connector (X2)Standard RJ45 connector (optional: IP68)
Housing
Aluminium desktop housingoptional: DIN rail adapter
Dimensions (mm)224 x 150 x 60
Communication interfaces
TCP/IPEBIS-Protocol
.NET library
Web interfaceConfiguration, Firmware update, etc.
Cloud SupportMQTT, Azure, AWS
Safety features
Status LEDsPower supply, network status, error
Encryption protocolTLS

EBIS-TF8-IO16 Specifications

General
Number of connectors8 (no Multiplexing)
Connectors (1-8)5-pin. M18 circular female connector
Sensor typeHalf-Bridge or LVDT
TypeSingle-Ended or differential
Output frequencyUp to 20 kHz
Output amplitudeUp to 20 VPP
Features: internal filters, temperature compensation,
programmable output frequency and amplitude
Inputs ADC (X3 Option)
Inputs ADC (X3 Option)4 (no Multiplexing)
Input voltage± 10V (common reference voltage)
Input impedanceCa. 560 kOhm
Digital Inputs/Outputs
Number of inputs8
Galvanic isolation500 VAC
Nominal voltage (VSUPPLY)24 VDC
Power supply11 V – 35 V
ESD2,5 kV HBM JESD22-A114-B
1,5 kV CDM ESD STM5.3.1-1999
Informations:
Digital interface IEC61131-2 Type 1, PLC interface, Status LEDs,
external power supply needed (VSUPPLY and GND)
Number of outputs8
Typ0,625 A High-Side Switch
Galvanic isolation500 VAC
Nominal voltage (VSUPPLY)24 VDC
Power supply11 V – 35 V
ESD2 kV HBM JESD22-A114-B
1 kV CDM ESD STM5.3.1-1999
Informations:
Protected against short to VSUPPLY /overload/overvoltage,
PLC interface, for all types of resistive, inductive
and capacitive loads, Status LEDs,
external power supply needed (VSUPPLY and GND)

Specification depends on version

Versions

TypeDescriptionOder number
EBIS-TF8-IO16(HB)– 8 x Interface Half-Bridge
– 8 x Digital Output
– 8 x Digital Input
– X3: Trigger-Input for e.g. footswitch
730
EBIS-TF8-IO16(HB/ADC)– 8 x Interface Half-Bridge
– 8 x Digital Output
– 8 x Digital Input
– X3: 4 independent ADC-Channels
731
EBIS-TF8-IO16(LVDT) – 8 x Interface LVDT
– 8 x Digital Output
– 8 x Digital Input
– X3: Trigger-Input for e.g. footswitch
732
EBIS-TF8-IO16(LVDT/ADC) – 8 x Interface LVDT
– 8 x Digital Output
– 8 x Digital Input
– X3: 4 independent ADC-Channels
733

Applications

  • Automotive industry
  • Machine tool industry
  • Medical production measurement
  • Optical industry